| 1 | Measure across ARC+ and ARC− on the DTHC. The input is polarity sensitive: ARC+ must be positive, ARC− negative. |
| 2 | Multiply the reading by the divider ratio set on the DTHC rotary switch. MASSO shows arc voltage only above 30 V. E.g. 1.5 V at 50:1 shows 75 V; at 16:1 the same 1.5 V gives 24 V, which shows as 0 V. |
| 3 | If nothing shows, test the DTHC with a 1.5 V AA battery or 3 V coin cell on the ARC input, rotary switch at position 0 (50:1). The plasma doesn't need to be on. Nothing connected: green LED on solid. Voltage applied: LED flashes quickly and the voltage shows on screen. |
| 4 | If the LED doesn't flash or no voltage shows, power-cycle the DTHC and test again. If it still fails, the DTHC may be faulty – contact MASSO Support. |