Spindle VFD examples
MASSO supports 0–10V signals, as well as clockwise and counter-clockwise signals, to directly control VFDs.
Follow the 7 steps shown in the video to connect your VFD.
For troubleshooting a VFD or spindle problem, refer to the Troubleshooting guide.
For additional VFD wiring diagrams, refer to the MASSO Forum VFD wiring section.
Connecting a VFD Forward/Reverse Input Using an Opto Output
Many VFDs use digital input terminals, such as:
- STF = Forward run
- STR = Reverse run
- SD / COM = input common
- PC / +24V = internal 24V supply
Different VFDs can use different input logic, so always check the wiring before connecting.
Step 1 — Check the VFD input type
Look in the VFD manual for one of these terms:
- Sink logic
- NPN input
- Source logic
- PNP input
If the manual shows Sink / NPN logic, the input turns ON when the input terminal is connected to the common.
Example:
- STF - SD = Forward ON
- STR - SD = Reverse ON
If the manual shows Source / PNP logic, the input turns ON when +24V is applied to the input terminal.
Example:
- PC / +24V - STF = Forward ON
- PC / +24V - STR = Reverse ON
Step 2 — Test with a multimeter
Power the VFD, but keep the machine safe and motor disabled if possible.
Measure DC voltage between:
STF and SD / COM
If you measure around +24V, the input is most likely a sink / NPN input.
Use this wiring:
- Opto collector - STF or STR
- Opto emitter - SD / COM
If you measure around 0V, then measure between:
PC / +24V and STF
If you measure around +24V, the input is most likely a source / PNP input.
Use this wiring:
- Opto collector - PC / +24V
- Opto emitter - STF or STR
Step 3 — Manual test before wiring the opto
Before connecting the opto, test the VFD input with a short wire.
For sink / NPN input:
- Short STF to SD / COM = Forward ON
- Short STR to SD / COM = Reverse ON
For source / PNP input:
- Short PC / +24V to STF = Forward ON
- Short PC / +24V to STR = Reverse ON
Only short terminals that the VFD manual shows as valid control input terminals.
Do not short PC / +24V to SD / COM unless the VFD manual specifically says this is allowed.
Step 4 — PC817 / opto wiring
A PC817 output is a transistor, not a relay contact. Polarity matters.
General rule:
- Collector = more positive side
- Emitter = more negative side
For sink / NPN VFD inputs
- VFD STF / STR - PC817 collector
- VFD SD / COM - PC817 emitter
When the opto turns ON, it connects the input to the common.
For source / PNP VFD inputs
- VFD PC / +24V - PC817 collector
- VFD STF / STR - PC817 emitter
When the opto turns ON, it applies +24V to the input.
Step 5 — Forward and reverse safety
Use separate outputs for Forward and Reverse.
- Output 1 - Forward input
- Output 2 - Reverse input
Never turn ON Forward and Reverse at the same time.
Recommended control sequence when changing direction:
- Forward OFF
- Wait 200–500 ms
- Reverse ON
or
- Reverse OFF
- Wait 200–500 ms
- Forward ON
Important note
A PC817 is not a true dry contact. If the collector and emitter are swapped, some VFDs may still run because a small leakage current can trigger the VFD input.
For best universal compatibility, use a relay contact or PhotoMOS output when the VFD input type is unknown.
- Relay contact = behaves like a real switch
- PC817 output = polarity-sensitive transistor