Best practice when wiring MASSO
This document outlines recommended work practices when setting up and wiring your MASSO controller.
If you are unsure about any wiring—especially mains voltage equipment—always consult a licensed electrical technician.
Install a Fuse

General Wiring Practices
When connecting, disconnecting, or making wiring changes to MASSO, the mains power must be switched off. This ensures that accidental contact with a connection point during installation does not immediately damage the system.
After completing any wiring changes, all connections should be carefully checked before restoring power to confirm the system has been wired correctly.
Wiring should be carried out in a tradesman-like manner, with wires kept neat and securely captured within the screw terminals. Stray wire strands that are not properly secured can contact adjacent terminals and cause damage. Although bootlace ferrules are not required, their use can help keep wiring tidy and reduce the risk of loose strands.
Coloured wiring should be used where possible, and accurate records of all wiring connections between MASSO and external devices should be kept. This will greatly assist with troubleshooting if an issue occurs at a later time.
Auxiliary Power Terminals
The auxiliary power terminals on MASSO G3 are the red and black terminals labelled POWER and GND. These terminals are intended to provide logic-level power only and should be used exclusively for low-power devices.
If there is any uncertainty about whether to use the auxiliary power terminals or the positive and negative terminals of the DC power supply distribution point, the DC power supply distribution point should always be used, as this is the safest option.
A suitable application for the red auxiliary power terminal is supplying pull-up resistors for input signals. These resistors should be protected from accidental contact with other circuits. Using clear heat-shrink tubing is recommended, as it allows the resistor to remain visible while providing effective insulation.

Emergency Stop (E-Stop)
An E-Stop output labelled ES is provided on MASSO and may be used to drive a TTL relay module. This output allows external equipment such as drives, spindles, and other actuators to be disabled when an E-Stop is activated.
__ad61b7d9ba4b840414ef5d5d3859e4b7.png)
INFORMATION: Up to two MASSO relay inputs can be connected to the ES output. If additional relay contacts are required, a TTL relay may be used to drive a relay with multiple contacts, or multiple MASSO TTL relays may be wired as described in the E-Stop wiring documentation: EStop Wiring
VFD Wiring
The VFD must always be fully powered down before any wiring changes are made.
Plasma Wiring
Proper earthing is critical to the correct operation of a plasma machine. Correct earthing allows the arc to function as intended, improves cut quality, and reduces electrical noise that may interfere with THC operation and MASSO performance. The plasma system must be earthed in accordance with the manufacturer’s instructions and established best practices.
Control of External Mains-Powered Devices
Although the MASSO relay module is rated for 240 V at 5 A, it is not recommended to mix low-voltage and mains-voltage circuits on the same relay module. A safer and more robust approach is to use MASSO relay outputs to operate separate mains-rated relays that are installed elsewhere within the control cabinet. All mains relays should be grouped together and adequately shielded to prevent accidental contact.
Spanish
French
German
Simplified Chinese